Supply Units Type 8010, 8011, 8020, 8021 for AC Connections
 |
|
 |
|
| Supply Units Type 8010, 8011, 8020, 8021 for AC Connections |
 |
GENERAL DESCRIPTION:
The supply units allow for the operation of 24 VDC sensors, such as vent- and flow-captors, with AC supply voltage. The supply unit contains a 24 V DC transformer rectifier and a switching circuit with output relay with potential-free single pole double throw switching contact. An integrated LED displays the actual switching situation.
Housing Variations:
Type 8010, 8011: Macrolon housing with PG screwing for sensor, supply and output connection for wall mounting. For application where an AC Connection is available.
Type 8020, 8021: Clamp housing for standard bar as per DIN 46277 and DIN EN 50022 for the installation in switch cabinets or similar |
| Supply Unit Variations:
Type 8010, 8020: For PNP-switching sensors or sensors with analog output signal. On connection of an analog signal to the input of the Supply Unit a switch signal is activated which controls an integrated relay when a fixed threshold of 50% of the max. input signal is reached. This provides the possibility, when connecting flow and vent-captors with adjustable measuring range, to vary the switching point on a large scale; e.g., for the flow-captor 4114.30 related to water at flow velocity between 10 cm/s and 100 cm/s, -resp. for the vent-captor 3202.30 related to air between 50 cm/s and 15 m/s
Type 8011, 8021: For NPN-switching sensors. These units trigger the output relay directly from the switching output of the sensor.
Technical Data
| Type |
8011/8021 |
8010/8020 |
| Sensor output |
NPN |
PNP or analog |
Connecting Data for captor
| Supply |
24V DC, max. 120 mA, short circuit protected |
| Signal input |
UEon ≤ 6 V
UEoff ≥ 18.5V |
Ri approx. 500 Ohm,
Ie limited to 15 mA, threshold switch 12 mA,
hysteresis ± 0.8mA |
Contact Data of Relay
| Switching voltage max. |
30 V DC/240 V AC |
|
Switching current max. |
2.5A AC/DC |
Mechanical Data
Protection standard
|
8010, 8011: macrolon housing IP65/DIN 40050
8020, 8021: clamp housing IP40*
8020K, 8021K: clamp housing with air gaps IP20*
*(Clamps: IP20 and contact protected accord. to VDE 0100 part 750 and VBG4)
Air gap and creepage distance according to VDE 0110 Group C, 380 VE
|
| Sizes ( l x w x h ) and Mass |
8010, 8011: macrolon housing: (120x80x55) mm, 440 g
8020,8021: clamp housing: (55x75x110) mm, 350 g |
Electrical Data
| Type 80--/ |
12 V DC |
24 V DC |
48 V DC |
24 V AC |
115 V AC |
230 V AC |
| Voltage tolerance |
±10% |
±10% |
+20%/-30% |
±10% |
+6%/-15% |
+6%/-15% |
| Power consumption |
max. 6 W |
max. 6 W |
max. 6 W |
max. 6 VA |
max. 6 VA |
max. 6 VA |
| Internal protection |
0,5 T |
0,4 M |
0,4 M |
0,5 T |
0,1 T |
0,05 T |
Basic circuit diagrams
24 V AC-, 115 V AC-, 230 V AC Types






|
|